MOD-0100 Modulating Output Module
Overview
Diverse modulating types are available through the CPU-1000’s programming interface when using Modulating Expansion Modules:
Series: Modulating boilers will modulate up by percent in succession before additional boilers are required to fire.
Parallel: All Modulating boilers will modulate by percent in unison as boilers are required to fire.
Progressive: Used for multiple modulating boiler setup. Progressive will modulate the boilers in such a way that system efficiency is maximized and lag boilers are not cycled.
Features
- Series modulating type
- Parallel modulating type
- Progressive modulating type
Specifications
- 1 x Thermistor Input (10K Ohm)
- 1 x Misc. Input Signal (20-240VAC)
- 2 x Enable Output Relays (240VAC 10Amps)
- 2 x Mod Outputs (4-20mA, or 1-10v)
- Weight: 0.408Kg
- Dimensions: 100mm x 170mm x 70mm
- ETL Listings:
- Meets CSA C22.2 No. 24
- Meets UL Standard 873
- ETL Control No. 3068143
- Storage: 10°C to 40°C

MOD-0100